Sensor inputs: | 4-20 mA current interface for connecting sensors using two - or three-wire techniques LON® four-wire techniques galvanically isolated, data transmission 78 kbps |
Digital inputs: | Opto-isolated inputs, with galvanically isolated power supply |
Digital outputs: | Floating control outputs max. 230 V 4A 900 VA Warning outputs max. 230 V 6A 1400 VA |
Standard output signals: |
Serial interfaces RS 232 or RS 485 Analog Output 0 - 10 V or 0 (4) - 20 mA option - galvanically isolated LON® fieldbus, galvanically isolated, data transmission 78 kbps |
Battery operating time: | > 10 h with "mains fault" display, battery discharge protection > 1 h optionally, maintaining all Multitronik 592 functions |
Battery charging time: | 15 - 16 h, permanent charging system |
Power supply: | 24 V - 230 V, 130 VA , DC or AC |
Test certificate: | To German standards, according to VDI 2053 in conjunction with ADOS 592 CO Test numbers: 09-02-0120 09-95-0128 432-987615 |
Design and Operational Characteristics |
All information significant to operation is displayed in clear text on a 4-line, 16-digit display.This information includes the gas actual value, gas half - hourly average value, monitoring period, measuring point, sequence timing, alarm and faults ( or errors ).
The alarms and centralised malfunctions are all indicated by LED´s. A total 6 keys are used to operate the equipment. Four keys, together with menu-assistence, are used for defining the number of measuring points, the monitoring period and other parameters without any previous knowledge of programming. An electronic check of the units including the display of a single selected measuring point, is initiated by pressing a key. The siren after an alarm, can be cancelled either at the unit or as an option, externally. Digital switching outputs can be used for any ventilation and alarm control units; digital inputs are also available for external signals. For data communication RS 232 or RS 485 as well as current outputs 0 (4) - 20 mA or voltage outputs 0 - 10 V and the LON® field-bus are provided as standards interfaces. ADOS MULTITRONIK 592 is almost independent of mains supply networks. A line filter is provided as a standard. A charging unit for 24 V battery supply is integrated. The apparatus can be equipped with or without UPS (uninterruptable power system), according to the German VDI 2053 recommendations. The unit is delivered as standard, in a three-section sheet-steel housing with transparent lockable door, according to IP 54 standards. Control and power sections for the ventilator drive are mounted on an installation panel. |
Equipment Description |
The complete ADOS MULTITRONIK 592 gas measurement system consists of the following system components:
|
|
|
|